D-LE 103/D-UG 110/120 Flame Sensor and Control Unit
|
PRODUCT DESCRIPTION
The DURAG Flame Monitoring System from the DURAG Group consisting of a D-UG 110 or D-UG 120 Control Unit in combination with the D-LE 103 Flame Sensor is able to monitor flames of all burner types, fuels and combustion modes. The D-LE 103 Flame Sensor is available for different spectral ranges from UV to IR. UV flame sensors are mainly used for gas firings, whereas in the case of liquid and solid fuels it is the high emission in the IR region that will be evaluated.
These flame sensors have a range of spectral choice. The choices are 190 to 260 nm, 190 to 520 nm or 280 - 410 nm depending on the model. All blue-burning flames, e.g. gas flames whose portion of visible light is low may be monitored by these flame sensors.
Due to the potentially high risk of combustion processes every flame monitor should meet the highest standards for safety therefore the design of the D-UG 110/120 and D-LE 103 Flame Monitoring System is fail-safe and periodically performs self-checks. A dual channel microprocessor system ensures a safe operation of the flame monitor all the time.
|
PRODUCT SPECIFICATIONS
|
D-UG 110 Control Unit
|
|
Mains voltage
|
115/230 V AC, +10% -15%
|
Mains frequency
|
42-60 Hz
|
D.C. voltage
|
24/48 VDC ±20%
|
Power consumption
|
20 W
|
Permissable ambient temperature
|
-200C to +600C (00F to 1400F)
|
Safety time
|
1 s (other times on request)
|
Flame Relay
|
SPDT (230 VAC, 2 A)
|
Status Relay
|
SPDT (230 VAC, 2 A)
|
Analogue Output
|
0/4...20 mA / 750 Ohms
|
Protection (EN 60529)
|
IP00
|
Weight
|
approx. 1 kg (2.2 lb.)
|
Mounting
|
19'' plug-in unit
|
D-UG 120 Control Unit
|
|
Power supply
|
24 VDC ±20%
|
Power consumption
|
5 W
|
Permissable ambient temperature
|
-200C to +600C (00F to 1400F)
|
Safety time
|
1 s
|
Flame Relay
|
SPST (230 VAC, 2 A)
|
Status Relay
|
SPST (230 VAC, 2 A)
|
Analogue Output
|
0/4... 20 mA / 200 Ohms
|
Protection (EN 60529)
|
IP20
|
Weight
|
approx. 0.5 kg (1.1 lb.)
|
Mounting
|
DIN-rail
|
D-LE 103 Flame Sensor
|
|
Supply voltage
|
20 VDC (from control unit)
|
Spectral sensitivity (depending on type of flame sensor)
|
190-1800 nm
|
Permissable ambient temperature
|
-200C to +600C (00F to 1400F)
|
Viewing Pipe Connection
|
G 11/4''
|
Purge Air Connection
|
G 1/2''
|
Optical Viewing Angle
|
60
|
Protection (EN 60529):
|
|
- cable version (-CG)
|
IP65 / NEMA 4X
|
- standard plug version (-P)
|
IP67 / NEMA 4X
|
- metal plug version (-MP)
|
IP54 / NEMA 3S
|
Weight
|
approx. 1.5 kg (3.3 lb.)
|
|
|